Daikin Altherma 3 GEO Series Installer's Reference Manual page 186

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents

Advertisement

10
|
Configuration
Balancing
Installer reference guide
186
#
Code
[9.5.1]
N/A
INFORMATION
If a heat pump failure occurs and Emergency is not set to Automatic (setting 1),
the room frost protection function, the underfloor heating screed dryout function,
and the water pipe antifreeze function will remain active even if the user does NOT
confirm emergency operation.
HP forced off
HP forced off mode can be activated to allow the backup heater to provide
domestic hot water and space heating. This is, for example, useful when the brine
circuit is not yet ready to be used. Cooling is NOT possible when this mode is
activated.
#
Code
[9.5.2]
[7-06]
NOTICE
Activating HP forced off mode will NOT stop or prevent the brine pump from
operating in the following conditions:
10 day brine pump operation is active
The Brine pump test run has been started
Passive cooling is active
Priorities
For systems with an integrated domestic hot water tank
#
[9.6.1]
[5‑02]
0: Manual
1: Automatic
2: auto SH reduced/DHW on
3: auto SH reduced/DHW off
4: auto SH normal/DHW off
Activation of the HP forced off mode
0: disabled
1: enabled
Code
Space heating priority: Defines
whether backup heater will assist the heat
pump during domestic hot water operation.
For optimal operation and lowest power
consumption, it is strongly recommended to
keep the default setting (0).
If the backup heater operation is limited
([4‑00]=0) and the outdoor temperature is
lower than setting [5‑03], the domestic hot
water will not be heated with the backup
heater.
Description
Description
Description
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12