5
|
Application guidelines
Underfloor heating or radiators – Wireless room thermostat
Installer reference guide
26
▪
Easy. You can easily set the desired room temperature via the user interface:
-
For your daily needs, you can use preset values and schedules.
-
To deviate from your daily needs, you can temporarily overrule the preset
values and schedules, or use the holiday mode.
Setup
B
b
A Main leaving water temperature zone
B One single room
a Receiver for wireless external room thermostat
b Wireless external room thermostat
c Remote outdoor sensor
▪
For more information about connecting the electrical wiring to the unit, see
"8.2 Overview
of
4
actuators" [
80].
▪
The underfloor heating or radiators are directly connected to the indoor unit.
▪
The room temperature is controlled by the wireless external room thermostat
(optional equipment EKRTR1).
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
External room thermostat for the main
zone:
▪
#: [2.A]
▪
Code: [C-05]
Benefits
▪
Wireless. The Daikin external room thermostat is available in a wireless version.
A
c
a
electrical
connections
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
for
external
and
Value
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
internal