Daikin Altherma 3 GEO Series Installer's Reference Manual page 247

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents

Advertisement

10/11
Field settings table
Breadcrumb Field code
Setting name
9.I
[C-04]
Bivalent hysteresis temperature.
9.I
[C-05]
What is the thermo request contact type for the main zone?
9.I
[C-06]
What is the thermo request contact type for the add. zone?
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
Brine pressure switch present?
9.I
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
9.I
[D-01]
Contact type of preferential kWh rate PS installation?
9.I
[D-02]
Which type of DHW pump is installed?
9.I
[D-03]
Leaving water temperature compensation around 0°C.
9.I
[D-04]
Is a demand PCB connected?
9.I
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
9.I
[D-07]
--
9.I
[D-08]
Is an external kWh meter used for power measurement?
9.I
[D-09]
Is an external kWh meter used for power measurement?
9.I
[D-0A]
--
9.I
[D-0B]
--
9.I
[E-00]
Which type of unit is installed?
9.I
[E-01]
Which type of compressor is installed?
9.I
[E-02]
What is the indoor unit software type?
9.I
[E-03]
What kind of heater?
9.I
[E-04]
Is the power saving function available on the outdoor unit?
9.I
[E-05]
Can the system prepare domestic hot water?
9.I
[E-06]
Is a DHW tank installed in the system?
9.I
[E-07]
What kind of DHW tank is installed?
9.I
[E-08]
Power saving function for outdoor unit.
9.I
[E-09]
--
9.I
[E-0B]
Is a bi-zone kit installed?
9.I
[E-0C]
--
9.I
[E-0D]
--
9.I
[E-0E]
--
9.I
[F-00]
Pump operation allowed outside range.
9.I
[F-01]
Above which outdoor temperature is cooling allowed?
9.I
[F-02]
--
9.I
[F-03]
--
9.I
[F-04]
--
9.I
[F-05]
--
9.I
[F-09]
Pump operation during flow abnormality.
9.I
[F-0A]
--
9.I
[F-0B]
Close shut-off valve during thermo OFF?
9.I
[F-0C]
Close shut-off valve during cooling?
9.I
[F-0D]
What is the pump operation mode?
└─ Brine freezing temperature
9.M
[A-04]
What is the brine anti freeze temperature?
4P569818-1A - 2019.10
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/O
R/O
R/O
R/O
R/W
R/O
R/O
R/O
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
2~10°C, step 1°C
3°C
0: -
1: 1 contact
2: 2 contacts
0: -
1: 1 contact
2: 2 contacts
0: LWT control
1: Ext RT control
2: RT control
0: No
1: Outdoor sensor
2: Room sensor
0: Normally open
1: Normally closed
0
0: Not present
1: Present
0: None
1: BSH only
2: BUH only
3: All heaters
0: No
1: Active open
2: Active closed
3: Safety thermostat
0: No
1: Secondary rtrn
2: Disinf. Shunt
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
0: No
1: Pwr consmp ctrl
0: Forced off
1: As normal
0
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
0
2
0~5
5: GSHP
1
0: Reversible (*1)
1: Heating only (*2)
4: 9W
0: No
1: Yes
0: No
1: Yes
0: No
1: Yes
1: Integrated
0: disabled
1: Enabled
1
0
0
0
0
0: Disabled
1: Enabled
10~35°C, step: 1°C
20°C
3
5
0
0
0: Disabled
1: Enabled
0
0: No
1: Yes
0: No
1: Yes
0: Continuous
1: Sample
2: Request
0: 2°C
1: -2°C
2: -4°C
3: -6°C
4: -9°C
5: -12°C
6: -15°C
7: -18°C
Installer setting at variance with
default value
Date
Value
(*1) *X*_(*2) *H*