Daikin Altherma 3 R F Installation Manual

Daikin Altherma 3 R F Installation Manual

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

Quick Links

Installation manual
Daikin Altherma 3 R F
https://daikintechnicaldatahub.eu
EBVH11S18+23DJ6V
EBVH11S18+23DJ9W
EBVH16S18+23DJ6V
EBVH16S18+23DJ9W
EBVX11S18+23DJ6V
EBVX11S18+23DJ9W
EBVX16S18+23DJ6V
Installation manual
EBVX16S18+23DJ9W
English
Daikin Altherma 3 R F

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R F

  • Page 1 Installation manual Daikin Altherma 3 R F https://daikintechnicaldatahub.eu EBVH11S18+23DJ6V EBVH11S18+23DJ9W EBVH16S18+23DJ6V EBVH16S18+23DJ9W EBVX11S18+23DJ6V EBVX11S18+23DJ9W EBVX16S18+23DJ6V Installation manual EBVX16S18+23DJ9W English Daikin Altherma 3 R F...
  • Page 2 3P655197-2A...
  • Page 3 3P655197-2A...
  • Page 4: Table Of Contents

    Configuration wizard: Main zone......... 31 ▪ Format: Paper (in the box of the indoor unit) + Digital files on http://www.daikineurope.com/support-and-manuals/product- 7.2.6 Configuration wizard: Additional zone......31 information/ 7.2.7 Configuration wizard: Tank ......... 32 Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 5: Specific Installer Safety Instructions

    Daikin website (publicly accessible). recommended by the manufacturer. ▪ The full set of latest technical data is available on the Daikin ▪ Be aware that R32 refrigerant does NOT contain an Business Portal (authentication required).
  • Page 6: About The Box

    Indoor unit heater). ▪ At delivery, the unit MUST be checked for damage. Any damage MUST be reported immediately to the claims agent of the carrier. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 7: Installation Site Requirements Of The Indoor Unit

    ▪ Domestic hot water production: 5~35°C WARNING Make sure installation, servicing, maintenance and repair INFORMATION comply with instructions from Daikin and with applicable Cooling is only applicable in case of: legislation and are executed ONLY by authorised persons. ▪ Reversible models NOTICE ▪...
  • Page 8: Installation Patterns

    =1.86 m + Chimney height release Installation with chimney connected to the outside. The release height is not relevant. There are no requirements to the minimum floor area. Not applicable Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 9 ▪ Must be a permanent opening that cannot be closed. ▪ Must be ≥50% of A (minimum bottom opening area). nv-min Min. 50% ▪ Must be ≥1.5 m from the floor. of A nv-min (≥A nv-min EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 10 Ventilation openings must comply with A and with nv-min "Conditions ventilation openings" on previous page). Min. 50% Min. 50% ΔH1 of A of A nv-min nv-min (≥A (≥A nv-min nv-min Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 11 35.00 3.30 2.10 1.72 3.47 2.21 1.81 3.91 2.49 2.03 1.76 4.34 2.77 2.26 1.96 1.75 4.78 3.04 2.49 2.15 1.93 1.76 5.04 3.21 2.62 2.27 2.03 1.85 1.72 EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 12 Floor area of room A (m²) [! NOT room A + room B !] 5.00 10.00 15.00 20.00 25.00 30.00 35.00 1.66 1.86 2.06 2.26 2.46 2.66 2.86 3.06 Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 13: Opening And Closing The Unit

    4.3 kg, use the row of 4.4 kg. Total refrigerant charge (kg) (dm²) nv-min X 1 A 10.1 X 1 4 Y 10.4 10.6 10.9 11.1 11.3 11.5 3 Remove the switch box cover. 11.8 EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 14: To Lower The Switch Box On The Indoor Unit

    During the installation, you will need access to the inside of the irregularities. The maximum allowed deviation is 1°. indoor unit. To have easier front access, put the switch box lower on the unit as follows: Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 15: To Connect The Drain Hose To The Drain

    ▪ with a heat resistance of at least 120°C ▪ Insulation thickness Pipe outer diameter Insulation inner Insulation thickness (Ø diameter (Ø 9.5 mm (3/8") 12~15 mm ≥13 mm 15.9 mm (5/8") 17~20 mm ≥13 mm EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 16: Connecting Refrigerant Piping

    See the recommended procedure as described in "8.2  Checklist (valve, connections,…) MUST withstand following commissioning" [ 4  37]. during temperatures: INFORMATION The following illustration is an example and might NOT match your system layout. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 17: Connecting Water Piping

    "8.2.1 To check the minimum flow rate" [ 4  38]. NOTICE Electrical installation Install air purge valves at all local high points. DANGER: RISK OF ELECTROCUTION EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 18: About Electrical Compliance

    "6.3.9 To connect the power inputs" [ 4  24]. digital inputs consumption digital [9.B.1]=2 (External sensor = Room) Safety thermostat "6.3.10 To connect the safety [1.7] Room sensor offset thermostat (normally closed contact)" [ 4  25]. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 19: To Connect The Main Power Supply

    Wireless room thermostat ▪ Installation manual of the wireless room thermostat ▪ Addendum book optional equipment Wired room thermostat ▪ Installation manual of the wired room without multi-zoning base thermostat unit ▪ Addendum book optional equipment EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 20: To Connect The Backup Heater Power Supply

    2 kW 1N~ 230 V 9 A — (b)(c) 4 kW 1N~ 230 V 17 A 0.22 Ω (b)(c) 6 kW 1N~ 230 V 26 A 0.22 Ω 2 kW 3~ 230 V 5 A — 4 kW 3~ 230 V 10 A — 6 kW 3~ 230 V 15 A — Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 21: To Connect The Shut-Off Valve

    For more information, see the installer reference guide. Wires: 2×0.75 mm² Maximum running current: 100 mA 230 V AC supplied by PCB [2.D] Shut off valve unit" [ 4  13]): 1 Open the following (see "4.2.1 To open the indoor EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 22: To Connect The Electricity Meters

    X5M/6 and X5M/4; the negative polarity to X5M/5 and X5M/3. unit" [ 4  13]): 1 Open the following (see "4.2.1 To open the indoor 1 Top panel 2 User interface panel 3 Upper switch box cover Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 23: To Connect The Alarm Output

    A4P Installation of EKRP1HBAA is 2 User interface panel required. 3 Upper switch box cover 2 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 24: To Connect The Changeover To External Heat Source

    1 Top panel 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 25: To Connect The Safety Thermostat (Normally Closed Contact)

    The 2 incoming Smart Grid contacts can activate the following Smart respective terminals. Grid modes: Smart Grid contact Smart Grid operation mode Free running Forced off Recommended on Forced on EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 26 Screws for K1A and K2A Sticker to put on the high voltage wires Wires between the relays and X5M (AWG22 ORG) Wires between the relays and X10M (AWG18 RED) Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 27: After Connecting The Electrical Wiring To The Indoor Unit

    (via the unit), the configuration wizard starts to help you configure the system. High voltage Smart Grid contact 1 High voltage Smart Grid contact 2 EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 28: To Access The Most Used Commands

    The Advanced user pin code is 1234. Additional menu items for the screen and request to restart the system. user are now visible. When confirmed, the system will restart and recent changes will be applied. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 29: Configuration Wizard

    When the heat pump fails to operate, the backup heater can serve as an emergency heater. It then takes over the heat load either automatically or by manual interaction. a Main LWT zone EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 30: Configuration Wizard: Backup Heater

    50°C, An overpressure bypass valve can be integrated in the Daikin recommends NOT to disable the backup heater system. Keep in mind that this valve might not be shown second step because it will have a big impact on the on the illustrations.
  • Page 31: Configuration Wizard: Main Zone

    (e.g. heat pump convector). Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface (BRC1HHDA used as room thermostat). EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 32: Configuration Wizard: Tank

    NOT been reached. ▪ Main zone - Heating Only program a storage stop when tank heating is absolutely ▪ Main zone - Cooling undesirable. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 33: 2-Points Curve

    ▪ Change the offset to equally increase or decrease the temperature leaving water different ambient When offset is selected: set offset. temperatures. For example, if leaving water temperature is always Confirm changes and return to the submenu. EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 34: Using Weather-Dependent Curves

    At cold outdoor Slope Offset temperatures … temperatures … Only applicable in external room thermostat control. For more info zone" [ 4  34]. about the functionality, see "7.4.1 Main Cold ↑ — Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 35: Information

    ▪ 2: 2 contacts 7.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 36: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 37: Commissioning

    Next commissioning instructions in this chapter, a general ▪ Between the local supply panel and the indoor unit commissioning checklist is also available on the Daikin ▪ Between the indoor unit and the valves (if applicable) Business Portal (authentication required).
  • Page 38: To Check The Minimum Flow Rate

    3 Select a test from the list. Example: Heating. ▪ Bizone direct pump test (bizone kit EKMIKPOA or EKMIKPHA) ▪ Bizone mixed pump test (bizone kit EKMIKPOA or EKMIKPHA) Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 39: To Perform An Underfloor Heating Screed Dryout

    ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 40: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 41: Wiring Diagram: Indoor Unit

    Translation of text on wiring diagram Position in switch box English Translation English Translation (1) Main power connection (1) Main power connection Position in switch box Position in switch box EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 42 Smartgrid PV power pulse meter Smart Grid photovoltaic power pulse meter Switch box (7) Option PCBs (7) Option PCBs Alarm output Alarm output Changeover to ext. heat source Changeover to external heat source Max. load Maximum load Installation manual EBVH/X11+16S18+23DJ Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 43 A8P: X801M: 4-5 add: X2M: 30-35a 4 core signal signal main & add: X2M: 3-4 Only for Human Comfort Interface 2 core 2×0.75 X5M: 11-12 A14P: P1-P2 user interface communication 4D128798 EBVH/X11+16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643599-1B – 2021.10...
  • Page 44 4P643599-1 B 00000007 4P643599-1B 2021.10 Verantwortung für Energie und Umwelt...

Table of Contents