5.9 Connecting the PROFIBUS DP interface (410 DP only)
Boundary conditions
You must pay attention to the following boundary conditions when routing the bus cable for
indoor use (dA = external cable diameter):
Table 5- 9
Features
Bending radius for a single bend
Bending radius for multiple bends
Permissible temperature range for cable routing
Temperature range for storage and stationary operation
Additional references
For more information on the pre-assembled cables, refer to:
● Automation Systems for Machine Tools
5.9.5

Connecting PROFIBUS DP (interface X21)

Introduction
PROFIBUS cables are connected to the corresponding interface via a bus connector.
Connecting the bus connector
Proceed as follows to connect the bus connector:
1. Plug the bus connector into the module.
2. Screw the bus connector firmly into place.
3. If the bus connector is located at the start or end of a segment, you must connect the
Figure 5-4
Note
Make sure that the nodes at which the terminating resistor is located are always supplied
with voltage during startup and operation.
72
Boundary conditions for routing of PROFIBUS cables
Motion Control SIMOTION, SINAMICS S120 catalog and motors for production machines
catalog, PM21
terminating resistor (switch setting "ON").
Terminating resistor switched on and off
Boundary conditions
80 mm (10 x dA)
160 mm (20 x dA)
-5 °C to +50 °C
-30 °C to +65 °C
NC60 Catalog
SIMOTION D410
Manual, 02/2012