Single-channel switched I/O configuration at the PROFIBUS DP interface
The installation with single-channel switched I/O is possible with the ET 200M distributed I/O
device with active backplane bus and redundant PROFIBUS DP slave interface and with the
ET 200iSP distributed I/O device.
Figure 6-7
You can use the following interface modules for the I/O configuration at the PROFIBUS DP
interface:
Table 6- 3
Interface module
IM 152 for ET 200iSP
IM 153-2 for ET 200M
Each S7-400H subsystem is interconnected with one of the two DP slave interfaces of the
ET 200M over a DP master interface.
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
Single-channel switched distributed I/O configuration at the PROFIBUS DP interface
Interface modules for use of single-channel switched I/O configuration at the PROFIBUS
DP interface
Article No.
6ES7152-1AA00-0AB0
6ES7153-2BA82-0XB0
6ES7153-2BA02-0XB0
I/O configuration variants
6.5 Using single-channel switched I/O
67