Setup Screen
Screen 5: 5: 5: Flow
Setup
Setup
Screen
Use this screen to set your flow rate maximum and
minimum alarm values.
Enter the screen to set or change
preferences.
Press to activate a field for editing or
to accept the highlighted selection on a
menu.
Move to the right when editing number
fields. Press again to accept the entry
when all digits are correct.
Set your desired maximum (first data
field) and minimum (second data field)
flow rates. Flow rates outside of these
parameters will trigger an alarm.
Select (
) if you want the alarm to be
based on percent deviation from the
current active target flow rate. When
selected, the maximum and minimum
values shown above will automatically
update based on the selected +/- percent
amount and the current active Flow Rate
Target on the Run Screen.
46
Flow Rate
Rate
Flow
Rate
Key
Key
Key
Key
Key
Key
Set the +/- percent difference from the
flow target that will trigger an alarm.
Alarm Auto Clear Enable. If enabled,
when the flow rate returns to within the
flow limit set points, the flow rate alarm
will clear on the screen and on any
attached accessories such as a light
tower.
Select the type of alarm.
Advisory. System does not shut down.
It does not attempt to modify operation.
Event is logged.
Deviation. System does not shut down.
It may attempt to modify operation to
adjust to the conditions. Event is logged.
Alarm. System shuts down. Event is
logged.
Exit data editing.
Move between Setup Screens, fields on
a screen, or to increment/decrement the
digits when editing number fields.
3A6948A