Calibration Steps
1. Press
to enter Setup Mode.
2. Press
to move to Setup Screen 5.
3. Press
to enter the screen.
4. Press
to begin the calibration.
5. Dispense about 300–500 cc of material into a
graduated cylinder. The amount the system
measures will display in the measured volume
field
.
6. Press
to end the calibration.
7. Press
to get to the dispensed volume field
, then press
the amount of material in the cylinder.
8. After the volume is entered, the system calculates
the new k-factor and shows it on Setup Screen 5.
NOTE: To clear the counter and begin the
calibration again, press
another screen, then return to Setup Screen 4
and start over. If you press
the screen, the counter will continue from where
it is, without clearing.
9. Press
to exit the screen.
10. Press
to exit Setup Mode.

Set the Modbus Addresses

See Setup Screen 7. By default, the Modbus is
set to Off
. If you need the Modbus, set the
Modbus mode to SLAVE
value is between 1 and 247. The modbus address
corresponds to the address of the ProControl 1KE.
See Appendix A for further information.
3A2614H
to enter the field. Enter
, move briefly to
without leaving
. The address

Set the Flow Rate Percent

1. System Setup: See
set the upper and lower limit within which the
operator can adjust the flow rate. The settable
range is 0 to 99.9 percent, but the I/P pressure
transducer requires a minimum of 22 to 25 flow
rate percent target to start flow. Therefore, the
operational range is about 22 to 99.9 percent.
See Table 1.
Table 3
Flow Rate
I/P Current
Target
0–about 20
0–4.0 mA
percent
22%-25%
4.4–5.0 mA
11–12 mA
55% — 60%
20 mA
99.9%
2. Operator: See
Run Screen 1, page 24
the flow rate within the set limits.

Update the Software

Software updates are installed using a software token
(PN 16P892), which is sent automatically when a new
version of the software is released. Manual 3A1244
will accompany any necessary software updates.
Follow all instructions and warnings in Manual
3A1244 to update your ProControl 1KE software.
Operation
Setup Screen 2, page 27
Effect
No flow
Lowest flow
rate
Middle flow
rate
Highest flow
rate
to adjust
to