6 INSPECTION AND MAINTENANCE

6.6.3 Confirming error code

(k) Flowchart for when "AL"
""AL" (flashes 3 times)
occurrence.
The following shows the flowchart for when ""AL" (flashes 3 times)
Steady "S01" display" displays on 7-segment LED during operation.
"AL"
"S01" displays on 7-segment
LED.
Confirm details of error by Motion
CPU error batch monitor of
MT Developer2.
Remove the error cause of servo
amplifier, and then execute the servo
error reset (M3208+20n ON) or
re-turn on the servo amplifier power
supply.
Does "AL"
7-segment LED?
The error codes and error contents can be read using MT Developer2.
Refer to help of MT Developer2 for details of operating method.
"S01" displays on 7-segment LED
Steady "S01" display" displays at the servo error
"S01"
NO
disappear on
YES
END
6 - 29