The power-ON procedure is as follows:
For AC
1) Switch power ON.
2) Set CPU to RUN.
3) Turn ON the start switch.
4) When the magnetic contactor (MC) comes on, the output
equipment is powered and may be driven by the program.
(2) System design circuit example of the PLC I/O
(a) System design circuit example(when not using ERR terminal
of power supply module)
Input switched when
power supply established
Ym
RUN/STOP circuit
Interlocked with RA1
(Run monitor relay)
Yn
MC
Input module
Low battery alarm
(Lamp or buzzer)
L
ON when run by SM403
RA1
MC
Power to output equipment
switched OFF when the
STOP signal is given.
In the case of an emergency
stop or a stop caused by a
limit switch.
MC1
Interlock circuits as necessary.
Provide external interlock
MC2
circuits for conflicting
operations, such as forward
rotation and reverse rotation,
and for parts that could
damage the machine or cause
accidents if no interlock were
used.
Power supply
FOR AC/DC
Transformer
Fuse
CPU module
SM52
Ym
SM403
Yn
XM
TM
TM
MC1 NO M10
N0
M10
Program
START SW
RA1
MC
MC
STOP SW
RA2
Output module
Ym
Yn
Output module
MC2
MC1
For AC/DC
1) Switch power ON.
2) Set CPU to RUN.
3) When DC power is established, RA2 goes ON.
4) Timer (TM) times out after the DC power reaches 100[%].
(The TM set value should be the period of time from when
RA2 goes ON to the establishment of 100[%] DC voltage.
Set this value to approximately 0.5 seconds.)
5) Turn ON the start switch.
6) When the electromagnetic contactor (MC) comes on, the
output equipment is powered and may be driven by the
program. (If a voltage relay is used at RA2, no timer (TM) is
required in the program.)
3 - 6
Transformer
Fuse
DC power
(-)
(+)
Fuse
Set time for DC power
supply to be established.
RA2
Voltage relay is
recommended.
XM
Low battery alarm
(Lamp or buzzer)
L
ON when run by SM403
RA1
MC
MC
Power to output
equipment switched
OFF when the STOP
signal is given.
In the case of an
MC1
emergency stop or a
stop caused by a limit
switch.
MC2