7 EMC DIRECTIVES
Do not ground the cable clamp to the top of control panel. Doing so may lead to damage by drop of
screws, etc. during installation or removing the cable clamp.
(3) Cable clamp
It is also possible to ground the exposed shielded part of the cable to the panel
with the cable clamp.
• Ground the shield at a position 20 to 30cm (7.87 to 11.81 inch) away from the
module.
• When the cables pulled out from the control panel, ground the cables at a
position 5 to 10cm (1.97 to 3.94inch) away from the input/output hole of the
control panel with the cable clamp (AD75CK), etc.
Motion controller
Inside control panel
AD75CK
(1.97 to 3.94 inch)
• Cable clamp (Recommended product)
Manufacturer
Mitsubishi Electric
20 to 30cm
(7.87 to 11.81 inch)
5 to 10cm
Model name
AERSBAN-DSET
AERSBAN-ESET
AD75CK
CAUTION
7 - 7