HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
3.3
Mounting
Danger!
Danger to life from electric shock
Absent or insufficient insulation can result in electric shock.
Only connect supplies that provide protection against electric shock to power feed
modules (e. g. SELV or PELV).
Caution!
Property damage from use of isolators for Power Rail supply
Using the isolators for Power Rail supply can damage the isolators and make the
Power Rail fail.
Do not supply the Power Rail via isolators.
Mounting in the Non-Hazardous Area
Mounting the Device
Snap the device onto the DIN mounting rail in a vertical downward movement.
See figure below.
Mounting in Areas that Require the Equipment Protection Level Gc
Danger!
Explosion hazard from live wiring of non-intrinsically safe circuits
If you connect or disconnect energized non-intrinsically safe circuits in a potentially
explosive atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized non-intrinsically safe circuits in the absence of a
potentially explosive atmosphere.