HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Example
Characteristic 4 - 20 NE43, start value 2 bar, end value 10 bar
mA
20.5
20.0
4.0
3.8
0
1.9
Figure 4.1
Defining the Fault Current (fault message)
The type of fault current chosen will define how the current output transmits the fault
message to the controller.
1.
Select the type of fault current using the  or  buttons.
2.
Select the fault current down.
The fault message is indicated by a low current value.
3.
Select the fault current up.
The fault message is indicated by a high current value.
4.
Select the fault current hold.
The last measured value before the fault occurred is stored.
5.
Confirm your entry with OK.
2
10.25
10
bar
EN - 41