HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Activating Rebuild
If the connection to the field device has been lost, the localization phase can be performed
EN
with Rebuild without switching the device off and on again.
1.
2.
3.
4.
4.2.7
Current Outputs
In the Output menu, you have the option of defining current outputs 1 to 3 of the device. The
menu structure is identical for the three current outputs. Current output 1 is described as an
example. For information on relay contact outputs, see chapter 4.2.8.
38 - EN
Select On Rebuild with the or buttons.
Confirm your selection with OK.
The display On Rebuild flashes.
Press the OK button.
The device searches for connected field devices when booting.
Press the ESC button once or multiple times to switch to display mode.
OK →
Output
← ESC
▼
OK →
Iout1
Assignment
← ESC
▲
▼
Characteristic
▼
Start Value
▼
OK →
disabled
← ESC
▲
▼
▲
PV
▼
▲
SV
▼
▲
TV
▼
▲
QV
OK →
4 - 20
← ESC
▲
unlimited
▼
▲
4 - 20 NE43
OK →
see section
← ESC
▲