HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Fault Message
Calling up a Fault Message
1.
Use the or buttons to select the Fault message menu.
2.
If the fault message menu is activated, press the OK button once.
The Restart inhibit submenu is displayed.
3.
If the fault message menu is not activated, press the OK button twice.
The Restart inhibit submenu is displayed. The Fault message menu is activated
and is marked as On.
Fault (On)
Activating the Restart Inhibit
The restart inhibit is used to prevent momentary limit value violations from not being noticed
by operating personnel.
1.
Use the or buttons to select On.
2.
Confirm your selection with OK.
The relay status is retained after switching the relay.
3.
If you would like to reset the relay status, press the ESC or
button or restart the device.
The relay is reset. Exception: there is a fault message.
OK →
Restart Inhibit
← ESC
OK →
On
← ESC
▼
▲
OFF