HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
Connection KFD2-HLC-Ex1.D.4S
Danger!
Danger to life from electric shock
Working on live parts at voltages higher than 50 V AC or 120 V DC can result in electric
shock.
1.
De-energize the device.
2.
Secure the circuit against reconnection.
3.
Verify that the device is de-energized at all poles.
4.
Provide protection from adjacent live parts, if present.
The following connections are available:
•
Terminals 10/11: output I (relay 1 (NO contact))
•
Terminals 11/12: output II (relay 2 (NO contact))
•
Terminals 16/17: output III (relay 3 (NO contact))
•
Terminals 17/18: output IV (relay 4 (NO contact))
•
Terminals 7 to 9: output V, current output as source (7/8) or sink (7/9)
•
Terminals 13 to 15: output VI, current output as source (13/14) or sink (13/15)
•
Terminals 19 to 21: output VII, current output as source (19/20) or sink (19/21)
•
Terminals 22/24: connection of HART handheld
•
Terminals 23/24: power supply 24 VDC
EN
EN - 21