HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Selecting an Assignment
The values of the HART variables selected here (PV, SV, TV, QV) are monitored using a
relay contact output. The number of available variables depends on the HART field device.
When disabled is selected, the relay remains constant in a de-energized state.
1.
Select the desired HART variable using the or buttons.
2.
Confirm your selection with OK.
Defining Switching Characteristics
Selecting the switching characteristics defines the switching direction and the direction of
operation. See applications.
1.
Select the switching direction min or max with the or buttons.
2.
Confirm your selection with OK.
3.
Select the direction of operation passive or active with the or buttons.
4.
Confirm your selection with OK.
OK →
Mode
← ESC
▼
▲
OK →
Restart Inhibit
← ESC
▼
▲
OK →
Delay
← ESC
passive
▼
▲
active
On
▼
▲
OFF
0 s to 250 s
EN
EN - 45