HART Loop Converter KFD2-HLC-Ex1.D(.**)

Mounting and Installation

3
Mounting and Installation
Danger!
Explosion hazard from damaged electronic components
Premature wear of electronic components in a device that was previously used in a 
general electrical installation can cause sparks that can ignite the surrounding potentially
explosive atmosphere.
Never install devices that have already been operated in general electrical installations in
electrical installations used in combination with hazardous areas!
Danger!
Explosion hazard from pollution
An excessively polluted surface of the device can become conductive and consequently
ignite a surrounding potentially explosive atmosphere.
Ensure that you install the device only in environments with a pollution degree 2 or better
according to IEC/EN 60664–1.
3.1

DIN Mounting Rail

The devices are mounted on a 35 mm DIN mounting rail according to EN 60715.
Figure 3.1
Example: DIN mounting rail UPR-MR (35 mm x 15 mm)