HART Loop Converter KFD2-HLC-Ex1.D(.**)
Operation
5.1
Indicators during Operation
The isolated barrier displays the following operating modes and fault messages during
operation.
Status Indicators
LED
Green LED
Red LED
Yellow
LEDs
Table 5.1
Status
Description
Off
No power supply
Flashes regularly
Start-up phase, self-test
On
Normal function
Flashes briefly
Displays a single HART fault message received by the field device
Flashes regularly
Invalid HART data (missing communication or fault in the
field device)
On
Device self-test of isolated barrier detected a fault
On
Isolated barrier is in reset state, all other LEDs are off
On
For KFD2-HLC-Ex1.D.2W and KFD2-HLC-Ex1D.4S:
•
Output Out 1, relay energized
•
Output Out 2, relay energized
For KFD2-HLC-Ex1D.4S:
•
Output Out 3, relay energized
•
Output Out 4, relay energized