Diagnostics And Fault Clearance; Diagnostic Messages - Festo CPX-AP-I-4DI-M8-3P Instructions Manual

Digital input module
Table of Contents

Advertisement

Diagnostics and fault clearance

ID
Parameter
246
Fieldbus serial number
791
Product key
960
Firmware version
20000
Module code
20014
Input debounce time
0: 0.1 ms
1: 3.0 ms (factory setting)
2: 10 ms
3: 20 ms
20085
Measured value temperature AP-ASIC [°C]
20087
Current measured value of logic supply PS
[mV]
20088
Current measured value of load supply PL
[mV]
20093
Hardware version
1) ro = read only; rw = read write
Tab. 8 Parameter
10
Diagnostics and fault clearance
10.1

Diagnostic messages

ID hex (dec)
Message
01 
 01 
 010B
Short circuit/overload
|
|
(16843019)
in sensor supply
02 
 01 
 0016
Undervoltage in logic
|
|
(33619990)
supply PS 24 V DC
Festo — CPX-AP-I-4DI-M8-3P — 2019-07
Instance-
s
1
1
1
1
4
1
1
1
1
Description
A short-circuit/overload of the sensor supply was detec-
ted.
Remedy
Check connected load for correct function,
in particular for power consumption.
Check sensor and wiring.
Diagnost-
Error
ic status
Undervoltage of the logic supply PS 24 V DC was detec-
ted.
Remedy
Check logic supply PS.
Diagnost-
Warning
ic status
Error
Data
Access
1)
type
UINT32
ro
CHAR
ro
CHAR
ro
UINT32
ro
UINT8
rw
INT16
ro
UINT16
ro
UINT16
ro
UINT8
ro
Arraysize
12
30
9