[0] *
Normal operation
[1]
Control card test
[2]
Initialisation
[3]
Boot mode
14-50 RFI Filter
Option:
[0]
Off
[1] *
On
15-43 Software Version
Range:
0 N/A*
[0 - 0 N/A]
LCP read-out: Control Card OK.
Disconnect the mains supply and remove the test plug. The green LED on the Control Card will light
up.
If the test fails:
LCP read-out: Control Card I/O failure.
Replace the frequency converter or Control card. The red LED on the Control Card is turned on. Test
plugs (connect the following terminals to each other): 18 - 27 - 32; 19 - 29 - 33; 42 - 53 - 54
Initialization
Select
[2] to reset all parameter values to default settings, except for par. 15-03
Up's
Over Temp's
, par. 15-04
, and par. 15-05
the next power-up.
Par. 14-22
Operation Mode
will also revert to the default setting
Function:
Off
Select
[0] only if the frequency converter is fed by an isolated mains source (IT mains).
In this mode, the internal RFI filter capacitors between chassis and the mains RFI filter circuit are
cut-out to reduce the ground capacity currents.
Select
On
[1] to ensure that the frequency converter complies with EMC standards.
Function:
View the combined SW version (or 'package version') consisting of power SW and control SW.
®
MG.33.AG.02 - VLT
is a registered Danfoss trademark