These default notification classes match the default notification classes of the EBI
central.
Each recipient assigned to a notification class will receive the datapoint alarm
triggered by the selected notification. But, alarms will only be generated for the
enabled transitions (To-Normal, To-OffNormal, and/or To-Fault) of a recipient. Each
enabled transition will be propagated with the selected notification (see also "Alarm
and Event Priority Classification" section).
This connection has not to be mixed up with the transitions selected under
Transition Events (see "Transition Events" section).
Datapoint Type
User Interface
Editing
Equivalent
The notify type can be defined and changed in CARE. In the Excel Web HTML
Interface, the notify type (alarm type) is displayed only.
For all notification classes, the notify type ´Alarm` must be used.
According to the BACnet Specification, events can be of the type ´alarm` or ´event`.
On the EBI, alarms will be graphically indicated by blinking in the status line and
shown in the alarm summary. Events will not be indicated in the status line and will
be shown in the event summary.
See also "Alarm Type" section.
Datapoint Type
User Interface
Editing
Equivalent
Shows the name of the NV, e.g. NViInsideAirTemp , that is mapped to the
datapoint.
Datapoint Type
User Interface
Editing
Equivalent
Shows the type of the mapped NV, e.g. SNVT_temp.
See also "Input NV" and "Output NV" sections.
Datapoint Type
User Interface
62
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
Alarm Type
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
USER GUIDE

Notify Type

CARE
x

NV Name

CARE
x

NV Type

CARE
x
Input NV, Output NV

Out Of Service