USER GUIDE
NOTE: If the checkbox is unchecked, no start date can be selected. This
means that the schedule is valid on any date up to and including the
end date.
Click the Valid Until checkbox and select the end date from the drop-down list
box.
NOTE: If the checkbox is unchecked, no end date can be selected. This
means that the schedule is valid on any date from the start date on.
NOTE: If both checkboxes are disabled, the schedule is always valid.
21. From the Priority for Writing drop-down list box, select the priority between 9
and 16 (lowest). The priority defines which priority the schedule will have in the
BACnet priority array.
22. From the Read Access level drop-down list box, select the user level that
should have read access for the schedule.
Schedules will only be displayed in the Excel Web HTML Interface if the read
access level of the user is equal to or higher than the read access level of the
schedule.
23. From the Write Access level drop-down list box, select the user level that
should have write access for the schedule.
NOTE: Creating, editing, deleting and copying of schedules in the Excel Web
HTML Interface is only possible if the user's write access level is equal
to or higher than the write access level of the schedule.
24. Click the SUBMIT button.
25. Continue by clicking the Values tab.
Here you can do the following:
• Change details of switched properties (point)
• Define a schedule default value
• Override the present value (Manual)
161
FALCON
EN2Z-0962GE51 R0715