FALCON
Reference Points
Reference Input Points
BACnet-Bus
CONTROLLER A
Plant A1
Source Point
Physical Point or
Value Point
NOTE:
Controllers / 3rd Pary Devices can be in the same or in different projects.
EN2Z-0962GE51 R0715
The read access level can be defined and changed in CARE only. In the Excel Web
HTML Interface, the read access level is displayed only.
The read access level assigned to a datapoint determines which user level can read
values (properties) of that particular datapoint on the Excel Web HTML Interface.
A user who has a user level equal to or higher than the assigned read access level
of the datapoint, will have this access right enabled in the Excel Web HTML
Interface, all others will not (for further details, please refer to the User
Administration section).
Datapoint Type
User Interface
Editing
Equivalent
The reference property of a reference input point provides the source (BACnet
object) which passes the value to the reference input point. The reference property
of a reference output point provides the source (BACnet object) which passes the
value to the reference output point.
Sources can be any point of any Excel Web controller and 3
of the project.
Reference points are a type of software point that can share point information
across plants. If plants are located in different controllers, the point information will
be automatically transferred across the BACnet bus.
Reference input points receive information from a point in another plant of the same
controller (internal reference) or of another plant in another controller or 3
device (external reference). Controllers and 3
same or in different projects (for detailed procedure see CARE User Guide EN2B-
0182GE51).
Each reference input is associated with a physical or value datapoint (source point)
somewhere in a plant residing in a controller on the bus. The source point cannot be
a receiver point and source point and receiver point cannot reside in the same plant.
Data
Plant A2
Receiver Point

Reference

Input Point
Fig. 14. Data exchange between plants via reference input points
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
rd
Data
Plant B1
Source Point
Physical Point or
Value Point
66
USER GUIDE
Reference
CARE
x
rd
-party BACnet device
- party devices can reside in the
CONTROLLER B / 3rd Party DEVICE
rd
- party