Last Transition; Lon Point; Low Limit Enable - Honeywell Centraline FALCON User Manual

Table of Contents

Advertisement

FALCON
EN2Z-0962GE51 R0715
Datapoint Type
User Interface
Editing
Equivalent
Shows the date when the last transition was performed.
Datapoint Type
User Interface
Editing
Equivalent
Defines in CARE if the datapoint should be mapped to a NV.
Input points can only be mapped to input NVs and output points can only be
mapped to output NVs.
NOTE: If an output point is defined as "with switches", CARE will automatically
map an input NV to that output point. The input NV will be used for sending
the manual switch state a value from the I/O-board to the Excel Web
controller. The value of the manual switch is reflected at priority 1 in the
priority array of the datapoint.
See also "Direction" section
Datapoint Type
User Interface
Editing
Equivalent
The Low Limit Enable property defines the low limit for the creation of alarms of
analog points. The following conditions must be true for the system to generate an
alarm:
• The present value falls below the low limit and this condition remains present for
at least the defined alarm delay (time)
• Transition events ´To-OffNormal` and ´To-Normal`are enabled
• Notification class (urgent, high or low) is allocated to this point
• Notify type is set to ´Alarm` (not ´Event`)
If all of these conditions are true, then an alarm of event type ´To-Off-Normal` is set
off.
The Low Limit can be predefined in CARE and changed in the Excel Web HTML
Interface later.
NOTE:
According to the BACnet standard, disabling the Low Limit only disables the
reporting of the Low Limit Alarm onto the BACnet bus.
When the Low Limit is exceeded, the datapoint will still be "in Alarm", and if a
BACnet front-end is polling the alarms of a BACnet controller, also datapoints with
Low Limit disabled will be displayed on the BACnet front-end as being "in Alarm".
60
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
Direction
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
x
USER GUIDE

Last Transition

CARE

LON Point

CARE
x

Low Limit Enable

CARE
x

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents