Datapoints; Physical Datapoints; Value Datapoints - Honeywell Centraline FALCON User Manual

Table of Contents

Advertisement

FALCON
Analog Inputs
Analog Outputs
Binary Inputs
Binary Outputs
Multi-State Inputs
Multi-State Outputs
Pulse Converter
EN2Z-0962GE51 R0715
An Excel Web® controller supports up to 600 physical datapoints and an unlimited
number of value datapoints.
A datapoint has different properties according to its type. Properties are displayed
and can be modified via a standard browser on operator interfaces such as laptops,
desktop PCs, or panel PCs. Properties contain information about the given
datapoint. Among many more, this information could be:
• Present value
• Transition events
• Descriptions
• Input limits values
• Operating status
• Elapsed run time
The following sections provide more-detailed information about the different kinds of
datapoints and datapoint properties and explain which properties are assigned to
which datapoints.
In addition, the Excel Web controller has two Integrated I/Os:
Binary Output
• potential-free relay, SPST (single pole single throw), normally open, 24 Vac +/-
20%, max. 2 A permanent load
• application-driven
• 1 "active" LED, illuminated when contacts closed
The binary output can be used for connecting an alarm buzzer.
Binary Input
• potential-free contact, max. 36 Vdc
• application-driven
• 1 "active" LED, illuminated when contact closed
Physical datapoints are inputs and outputs attached to hardware devices like
sensors and actuators.
The following are examples of physical datapoints:
NTC, PT 1000, PT 3000, BALCO Sensors (PT 3000/BALCO), standard 0...10 V / 0
(4)...20 mA input, to connect outside air temperature sensors, for example.
Outputs with a continuous 0...10 V output signal for controlling continuous actuators
Inputs for processing voltage-free signals (switches, contacts, counters).
Outputs for driving three-position actuators, for example, a damper motor; two
position devices, for example, a circulation pump; and pulsed outputs
Inputs used for equipment feedback (Automatic, On, Off)
Outputs controlling multi-stage fans (0, 1, 2, 3)
Digital inputs for processing pulsed signals up to 20 Hz (depending on I/O module
specifications), for example, metered energy consumption.
42
USER GUIDE

DATAPOINTS

Physical Datapoints

Value Datapoints