Download Print this page
Honeywell Compact Corona Series Product Data

Honeywell Compact Corona Series Product Data

4-way rotary mixing valves

Advertisement

Quick Links

APPLICATION

The "Corona" series of Compact Rotary valves and
Actuators provide integrated mixing of boiler supply, boiler
return, loop supply, and loop return water in hydronic
heating systems. The V5442 is very effective for low
temperature loops such as radiant floor heating.
The V5442 4-way valve can mix both loop supply water
and boiler return water simultaneously to control loop supply
temperature and boiler shock or flue gas condensation
protection. They may be plumbed in either a direct mixing
or injection configuration.
The effective Cv of the valves is increased when piped in
an injection configuration.
Copyright © Honeywell Limited/Limitée • All Rights Reserved
V5442N Compact
4-way Rotary Mixing Valves

FEATURES:

• 4-way mixing action for closed hydronic heating systems.
• Mixes loop supply with boiler supply and loop return.
• Mixes boiler return with boiler supply and loop return.
• Optimized mixing characteristics for most accurate
control.
• Cast iron body; chrome plated plug.
• NPT threads.
• Suitable for manual or automatic control.
• "Universal" body orients either to the left or right to
match piping.
• Functional replacement for Centra ZRK-series of
compact 4-way mixing valves.
• Can be automated with M6063 actuator.
Application ............................................................................1
Features..................................................................................1
Specifications ........................................................................2
Ordering Information ..............................................................2
Installation ..............................................................................3
Settings ..................................................................................5
Operation................................................................................5
Checkout and Test ................................................................5
Troubleshooting......................................................................6
PRODUCT DATA
Contents

Advertisement

loading

Summary of Contents for Honeywell Compact Corona Series

  • Page 1: Table Of Contents

    The effective Cv of the valves is increased when piped in an injection configuration. Contents Application ................1 Features..................1 Specifications ................2 Ordering Information ..............2 Installation ................3 Settings ..................5 Operation................5 Checkout and Test ..............5 Troubleshooting..............6 Copyright © Honeywell Limited/Limitée • All Rights Reserved...
  • Page 2: Specifications

    Honeywell Inc. 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000 In Canada – Honeywell Limited-Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
  • Page 3: Installation

    V5442N “Corona” 4-way Compact Rotary Mixing Valves — INSTALLATION INSTALLATION 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. When Installing this Product . . . 3. Installer must be a trained, experienced service technician. 4.
  • Page 4 V5442N “Corona” 4-way Compact Rotary Mixing Valves — INSTALLATION Fig. 4 Valve and handle installation for other piping configurations A. Boiler supply enters B. Boiler supply enters C. Boiler supply enters D. Boiler supply enters from left, mixed output from right, mixed output from bottom, mixed from bottom, mixed exits from top.
  • Page 5: Settings

    V5442N “Corona” 4-way Compact Rotary Mixing Valves — SETTINGS • OPERATION • CHECKOUT Fig. 7 Primary-secondary loop installation Fig. 8 Injection configuration. V5442 must be sized to secondary LOOP flow; acts V5442 valve always has flow from and to boiler. as balancing valve.
  • Page 6: Troubleshooting

    If the valve stem starts to leak, replace the O-ring as shown in Fig.9. Home and Building Control Honeywell Inc. Honeywell Limited-Honeywell Limitée 1885 Douglas Drive North 155 Gordon Baker Road Minneapolis, MN North York, ON...

This manual is also suitable for:

Compact corona v5442n