FALCON
EN2Z-0962GE51 R0715
Equivalent
Defines the value that will be written to the present value, if the priority list is empty
which means that no other value is present in the priority list. The relinquish default
value allows starting up a control system with a defined status/value. The relinquish
default value is predefined in the application in CARE and can be changed in the
Excel Web HTML Interface.
For further information on priority levels and command priorities, please refer to the
"Priority Level" section.
Datapoint Type
User Interface
Editing
Equivalent
Defines, which transition type will be reported, that is, which transition should be
saved in the alarm buffer and in the alarm list in the HTML Interface.
See also "Transition Events" section.
Datapoint Type
User Interface
Editing
Equivalent
Resets the current value of the pulse converter or the runtime counter of a binary
output to a specific value. The counting will restart.
See also "Current Value" section.
Datapoint Type
User Interface
Editing
Equivalent
Shows the runtime of the connected device. The runtime (active time) can be
changed by reset.
The runtime can be reported as follows:
In CARE, use the IDT statement to read the ´Elapsed Active Time` property of a
datapoint. Compare this value to a limit value and use an additional point to report
an alarm.
Datapoint Type
User Interface
Editing
Equivalent
68
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
x
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
x
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface

"Reset to"

AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
USER GUIDE

Reporting

CARE
x
Transition Events
Reset to
CARE

Runtime (Active Time)

CARE

Scaling Factor

CARE
x