Nr.
Analog Event States
1
High Limit to Normal
2
Low Limit to Normal
3
Fault to Normal
4
Normal to High Limit
5
Normal to Low Limit
6
Low Limit to High Limit
7
High Limit to Low Limit
8
Fault to High Limit
9
Fault to Low Limit
10
Normal to Fault
11
High Limit to Fault
12
Low Limit to Fault
Datapoint Type
User Interface
Editing
Equivalent
The alarm delay determines how long a ´To-Off-Normal` or a ´To-Normal` transition
must exist before an alarm is generated. Entering an alarm delay time of 10 seconds
means that the limit value must be exceeded for at least 10 seconds before this
datapoint generates an alarm. If the limit value only lasts for 7 seconds, then no
alarm occurs. The alarm handling for a datapoint can be completely disabled by
setting the alarm delay time to a value of 100000 or higher.
Datapoint Type
User Interface
Editing
Equivalent
For the property ´Alarm text`, CARE allows entering personalized alarm texts for the
different event states of an analog or digital point. The assigned alarm text is shown
with the alarm, which is caused by the corresponding transition event.
Alarm texts can have 256 characters at maximum with no restriction on the used
character type.
Analog points have twelve, Digital points have six possible event states. The
following table shows the event states and examples for alarm texts:
Alarm Text Example
Value below High Limit
Value above Low Limit
Sensor OK
Value above High Limit
Value below Low Limit
Sensor Break
Sensor Break
Sensor Break
Datapoint Type
User Interface
Editing
Equivalent
According to the BACnet Specification, events can be of the type ´alarm` or ´event`.
On the EBI, alarms will be graphically indicated by blinking in the status line and
shown in the alarm summary. Events will not be indicated in the status line and will
be shown in the event summary.
47
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
x
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
Digital Event States
Fault to Normal
Normal to Fault
Off-Normal to Normal
Normal to Off-Normal
Fault to Off-Normal
Off-Normal to Fault
AI AO AV BI BO BV MI MO MV PC RI RO
HTML Interface
-
FALCON
CARE
X

Alarm Text

CARE
X
Alarm Text Example
Input OK
Input Failure
Input back to Normal
Input Change to Alarm

Alarm Type

CARE
X
Notify Type
EN2Z-0962GE51 R0715