Ul611/Ul1610 Central Station Burglary Alarm; California State Fire Marshal (Csfm) And Ul Residential Fire Battery Backup Requirements - Honeywell VISTA-128BPEN Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Table of Contents

Advertisement

Vista-128BPEN Installation and Setup Guide

UL611/UL1610 Central Station Burglary Alarm

Follow the instructions for UL609 Local installations given above.
For Systems without Line Security:
You must use the VISTA-128BPEN' dialer with a 7845i-ent Communicator.
Connect the control's burglary/audible panic alarm trigger (on J7 header) and the 659EN's phone line monitor
output to the 7845-ent. The 7845i-ent will send a report to the central station when a telephone line fault condition
is detected.
Also connect the 7845i-ent's radio fault output to one of the VISTA-128BPEN' EOLR-supervised zones (i.e., 1-8).
Program this zone for a trouble by day/alarm by night (type 05) or a 24-hour alarm (type 07, 08) response to radio
faults.
Program the control's dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports.
For Systems with Line Security:
Follow the instructions for Systems without Line Security, except use the 7920SE in place of the 7845-ent.
Signal Receiving Centre Burglar Alarm Systems and Operations (Canada)
CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations.
CAN/ULC-S302, Installation and Classification of Burglar Alarm Systems for Financial and Commercial
Premises, Safes and Vaults; and CAN/ULC-S301.
California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup
Requirements
The California State Fire Marshal and UL have regulations that require all residential fire alarm control panels to have
backup battery with sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the
intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition.
The VISTA-128BPEN can meet this requirement without using a supplemental power supply, provided that the panel's
outputs (including the current drawn from the auxiliary power output terminals) are limited as shown below:
Output current is limited to 750mA maximum total auxiliary power, polling loop, and bell output current.
Maximum auxiliary current is 300mA (including polling loop current).
A 14AH battery is used. (Yuasa model NP7-12 recommended; use two connected in parallel.) A dual-battery harness
is provided with Honeywell No. 4100EOLR Resistor Kit (kit also contains EOL resistors having spade lug/heat
shrink tubing construction approved by UL and CSFM for fire zone usage). Both batteries fit inside the panel's
cabinet.