Section 3; Installing The Control; Mounting The Control Cabinet; Installing The Cabinet Lock - Honeywell VISTA-128BPEN Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.

Mounting the Control Cabinet

To mount the control cabinet, perform the following steps:
Step
Action
1
Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.
DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN
INSTALLED.
2
Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area
that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose.
To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2
U L
Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require
ATTACK RESISTANCE, use the cabinet included in the VISTA-ULKT kit.

Installing the Cabinet Lock

1.
Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.
2.
Position the lock in the hole (Figure 3-1), making certain that the latch will make contact with the latch bracket
when the door is closed.
When correctly positioned, insert supplied lock clip on the inside of the cabinet into the slots on the
3.
lock cylinder. Use ADEMCO Lock # N6277V1 and Lock Clip # P3422-2 (supplied).

Mercantile Premises Listing Guidelines

The panel door must be supervised. Mount the clip-on tamper switch (supplied) to the cabinet's right side wall as
shown in the diagram below, and wire it to one of the hardwire zones.
Use a bell with a tamper-protected housing such as the ADEMCO AB12M. The bell housing's tamper switch and
inner tamper linings must also be wired to the hardwire zone.
Assign the tampers' hardwire zone to a burglary partition. Program the hardwire zone for day trouble/night alarm
(zone type 5) when only one burglary partition is used. Program it for 24-hr. audible alarm (zone type 7) when more
than one burglary partition is used.
ULC
24-Hour audible alarm (zone types 6 and 7) is not approved for ULC applications.
All wiring between the bell and panel must be run in conduit. Remaining wires do not need to be run in conduit.
All wiring that is not run in conduit must exit from the knockout openings on the bottom or back of the cabinet.

Installing the Control

RETAINER CLIP
(NOTE POSITION)
LOCKED
RETAINER
SLOTS
RETAINER
CLIP
UNLOCKED
CABINET DOOR BOTTOM
Figure 3-1: Installing the Lock
S E C T I O N
3
3-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents