4.
Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds.
5.
All unused knockouts must be plugged (use the supplied disc plugs and carriage bolts).
6.
Must be used with a Listed burglar alarm sounding device/housing. Depending on the application, a compatible Listed
sounding device enclosure may also be required.

UL365 Police Station Connected Burglar Alarm

Follow the instructions for UL609 local installations given above.
For Systems without Line Security:
You may use the control panel's main dialer alone, or the 7845i-ent, 7847i, or IGSMV/IGSMHS Communications Device
alone.
When using the dialer, program it to send Burglary Alarm, Low Battery and Communicator Test reports. Field
be set to "0024" (or less) so that test reports are sent at least once every 24 hours.
For Systems with Encrypted Line Security:
The dialer must be used in conjunction with an iGSMHS Communications Device.

UL365/UL609 Bank Safe and Vault Alarm System

Follow the instructions for UL609 local installations above and Bank/Mercantile Safe and Vault (page 3-2) sections of this
manual.
Bell 1 Confirmation of Arming Ding (
Entry delays or any other delays to report alarms may not exceed 45 seconds.
Models 7845i-ent, 7847i, IGSMV, and IGSMHS or other compatible Listed communicators with 200-second supervision of
the communication channel must be used. A DACT is not to be used.
Bell Timeout must be programmed for 16 minutes min.
Two 17.2AH Batteries must be used for this application.
The main protective circuits, linings and attachments on the safe and vault, control units and alarm housing must be of the
normally closed circuit, fully supervised type.
Total current load must be 430mA max standby; 1.7A max alarm. Standby time must be at least 72 hours and 15 minutes.
To be installed inside the safe or vault.

UL1610 Central Station Burglary Alarm

Follow the instructions for UL365 local installations stated above, and follow the additional guidelines below.
For Systems without Line Security:
You must use the control panel's main dialer in conjunction with a 5140DLM, 7845i-ent, 7847i, or IGSMV/IGSMHS
Communications Device.
Program the dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports.
For Systems with Encrypted Line Security:
Follow the instructions for Systems without Line Security, but note that only an iGSMHS may be used as the secondary
Communications Device.

ULC Installation Requirements

The zone inputs of the control unit are considered Low Risk applications only.
The control unit must not be mounted on the exterior of a vault, safe or stockroom.
Subscriber control units capable of maintaining opening (disarming) and closing (arming) schedules must facilitate a
hardcopy printout of the opening (disarming) and closing (arming) schedule programming and of all the programmed
holidays.
Telephone service must be of the type that provides for timed release disconnect.
A server employed for control over network addressing, encryption or re-transmission, Must be designed to remain in the
"on state" at all times.
Encryption must be enabled at all times for active communications channel security.
For ULC Installations, refer to CAN/ULC-S302, Installation and Classification of Burglar Alarm Systems for Financial
and Commercial Premises, Safes and Vaults; CAN/ULC-S301, Standard for Central and Monitoring Station Burglar
Alarm systems and CSA 22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations.
16) must be set to 1 to on (enabled) (will automatically test bell).