FIELD
TITLE and DATA ENTRIES
Entry Delay #1 (partition-specific)
*09
Enter 02-15 multiplied by 15 seconds.
00 = 240 seconds (4 minutes).
Exit Delay #1 (partition-specific)
*10
Enter 03-15 multiplied by 15 seconds.
Entry Delay #2 (partition-specific)
*11
Enter 02-15 multiplied by 15 seconds.
00 = 240 seconds (4 minutes).
Exit Delay #2 (partition-specific)
*12
Enter 03-15 multiplied by 15 seconds.
Alarm Sounder Duration (Bell
*13
Timeout) (partition-specific)
Enter 01-15 multiplied by 2 minutes.
RS232 Input
*14
0 = Disable
1 = Enable
Keyswitch Assignment
*15
Enter 1-8 partition keyswitch is being used.
Enter 0 if the keyswitch is not used.
Confirmation of Arming Ding
*16
(partition-specific)
0 = disable
1 = enable
AC Loss Keypad Sounding
*17
0 = disable
1 = enable
5-2
EXPLANATION
Entry delay defines the delay time that allows users to re-enter the premises
through a door that has been programmed as an entry delay door and disarm
the system without sounding an alarm. The system must be disarmed within
this period or an alarm will occur. During entry time a distinct annunciation is
produced upon entry to warn the person entering the premise that entry delay
has begun. When the system is in Entry Delay, disarming is accomplished by
entering a valid user code. The annunciation silences upon entry of the first
digit of the user code. If an invalid user code is entered the annunciation
resumes.
NOTE: The delay may not exceed 45 seconds for UL installations. SIA
Guidelines: The entry delay time and Abort Window (field *88) combined
cannot exceed 60 seconds.
Exit delay defines the delay period that allows users to leave the premises
through a door that has been programmed as an entry/exit delay door after
arming the system without setting off the alarm.
NOTE: SIA Guidelines: The delay must be set for a minimum 60 seconds.
Entry Delay #2 is used for a secondary door requiring a longer delay than
those assigned to Entry Delay #1. During entry time a distinct annunciation is
produced upon entry to warn the person entering the premise that entry delay
has begun. When the system is in Entry Delay, disarming is accomplished by
entering a valid user code. The annunciation silences upon entry of the first
digit of the user code. If an invalid user code is entered the annunciation
resumes.
NOTE: The delay may not exceed 45 seconds for UL installations. SIA
Guidelines: The entry delay time and Abort Window (field *88) combined
cannot exceed 60 seconds.
Exit Delay #2 is used for a secondary door requiring a longer delay than those
assigned to Exit Delay #1.
NOTE: The delay may not exceed 60 seconds for UL installations. SIA
Guidelines: The delay must be set for a minimum 60 seconds.
Defines the length of time the Bell Output and the keypad's sounder will sound
for all audible alarms.
Must be minimum 16 minutes for UL Commercial Burglary installations. SIA
Guidelines: Must be minimum 6 minutes.
When enabled, sets input at J8 as an RS232 input.
Using the RS232 input for automation is not permitted in UL
U L
installations.
The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer
available as protection zone). The fire and panic alarm voltage triggers (J7)
automatically become ARMING and READY status outputs for the Keyswitch
LEDs.
Openings/closing report as user "0" if enabled in field *40.
If enabled, produces ½-second external alarm sounding ("ding") at the end of
exit delay (or after kissoff from the central station, if sending closing reports).
NOTE: If using a keyfob, when the button is pressed, either for arming or
disarming, the bell will ding indicating that the button is working.
Must be 1 for UL installations.
If enabled, sounding at the keypad (rapid beeping) occurs when AC power is
lost (sounding occurs about 2 minutes after actual AC loss).