System Communication and Operation

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Panel Communication with Central Station

This system accommodates several formats for reporting alarms and other system conditions to the
Central Station. The process of a successful transmission consists of both the method of
communication between the control panel and the Central Station receiver; and the actual way the
information is sent and displayed at the Central Station.
When the panel calls the Central Station receiver, it waits to hear a "handshake" frequency from the
receiver to confirm that the receiver is on-line and ready to receive its message. Once the panel hears
the handshake it is programmed to listen for, it sends its message. The panel then waits for a "kissoff"
frequency from the receiver acknowledging that the message was received and understood.
If the handshake frequency is not given or is not understood by the panel, the panel will not send its
message. Once the handshake frequency is received and understood by the panel, the panel sends its
message. If there is an error in the transmission (the receiver does not receive a "valid" message), the
kissoff frequency is not given by the Central Station receiver.
The panel makes a total of eight attempts to the primary telephone number and eight attempts to the
secondary telephone number (if programmed) to get a valid message through. If the panel is not
successful after its numerous attempts, the keypad displays COMM. FAILURE (on alpha keypads) or
FC (on fixed-word keypads).

Report Code Formats

The following chart indicates the types of (handshake/kissoff) frequencies that the panel supports and
the different formats that can be sent with each.
FORMAT
Low Speed
3+1, 4+1, 4+2
Sescoa/Rad
3+1, 4+1, 4+2
Robofon 8
Express
4+2
ADEMCO
Contact ID
Robofon
Contact ID
The following table describes each format in greater detail.
FORMAT TYPE
3+1 and 4+1
Standard Formats
3+1 and 4+1
Expanded Formats
Robofon 8
4+2 Format
ADEMCO and Robofon
Contact ID Reporting
Format
HANDSHAKE
TRANSMITS DATA
1400 Hz
1900Hz (10PPS)
2300 Hz
1800Hz (20PPS)
See Robofon 8 paragraph later in this section for details of the format.
1400–2300 Hz
DTMF (10 cps)
(multi-frequency)
1400–2300 Hz
DTMF (10 cps)
(multi-frequency)
2300 Hz
DTMF (10 cps)
(multi-frequency)
DESCRIPTION
Comprises a 3- (or 4-) digit subscriber number and a single-digit report
code (e.g., Alarm, Trouble, Restore, Open, Close, etc).
Comprises a 3- (or 4-) digit subscriber number and a two-digit report code.
The first digit is displayed on the first line. On the second line, it is repeated
3 (or 4) times and is followed by the second digit. This is the "expanded"
digit.
Comprises a 6-digit subscriber number and a 2-digit report code.
Comprises a 4-digit subscriber number and 2-digit report code.
Comprises a 4-digit or 10-digit subscriber number, 1-digit event qualifier
("new" or "restore"), 3-digit event code, 2-digit partition number, and 3-digit
zone number, user number, or system status number (see the following
page).
KISSOFF
TRANSMIT TIME
1400 Hz
Under 15 secs
(Standard report)
2300 Hz
Under 10 secs
(Standard report)
1400 Hz
Under 3 secs
1400 Hz
Under 3 secs
1400 Hz
Under 3 secs