FIELD
TITLE and DATA ENTRIES
Abort Window (partition-specific)
*88
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
Restore Report Timing
*89
0 = instant
1 = after bell timeout
2 = when system is disarmed
Secondary Subscriber Account
*90
Number (partition-specific)
Enter 00-09; B-F (11-15)
Check or TRBL Display
1*07
0 = CHECK
1 = TRBL
Zone Bypass After Disarm
1*11
0 = disable
1 = enable
Cancel Verify
1*15
0 = disable
1 = enable alarm output pulse upon kissoff of
Cancel report.
Lobby Partition
1*17
0 = none
1-8 = partition number
Affects Lobby (partition-specific)
1*18
0 = disable
1 = enable
Arms Lobby (partition-specific)
1*19
0 = disable
1 = enable
EXPLANATION
The Abort Window exists for all non-fire zones. All non-fire alarm reports are
NOT transmitted to the central station, if the code sequence is entered
within the Abort Window.
Otherwise, non-fire alarm reports are transmitted to the central station, if
programmed to do so, if the code sequence is not entered during the
Abort Window.
A prompt has been added to Zone Programming for each zone to
enable/disable this option (Abort Window Enable) with choices 0 = no abort
window, 1 = yes, use abort window according to field *88 selection. Each
non-fire zone MUST be programmed with a 0 for UL installations.
This field must be set to (2) for SIA installations.
Select the time when restore reports are sent after an alarm.
Must be 2 for UL installations.
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. Each number requires a 2-digit entry so as to allow entry of
hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data
only in the first three locations, and enter * in the fourth location.
NOTE: This field must be programmed if a secondary phone number is used
(field *34). This account number can be the same as the primary account
number.
Select whether the system should display TRBL or CHECK for trouble
conditions.
This field has eight entries, one for each partition. For each partition in which
"1" is entered, zones will remain bypassed after the system is disarmed..
NOTES:
For each partition in which field 1✳11 is enabled, the USER CODE + OFF will
no longer unbypass zones. To unbypass ALL zones, you must enter USER
CODE + # + 64. To unbypass zones INDIVIDUALLY, you must enter USER
CODE + 6 + zone number.
Any zone that was automatically bypassed by the system will be unbypassed
upon disarming of the system (e.g., STAY mode, Auto-STAY, etc.).
Vent zones and zones bypassed by a programmed Auto-Bypass schedule
(Timed Driven Event) are considered "manual bypasses" and will not be
unbypassed upon disarming the system.
Zones that were in a bypassed state at the time a System Shutdown is sent
from the Compass Downloading software will be unbypassed when the
System Shutdown is removed.
Select the Common Lobby Partition.
If enabled, causes lobby partition to disarm when this partition disarms.
NOTE: This partition must be armed before lobby can be armed.
If enabled, arming this partition causes the system to attempt to arm the lobby
partition automatically. To enable this field, field 1*18 must also be enabled
(partition-specific).
NOTES:
The lobby cannot be armed unless all partitions programmed for "affect" (field
1*18) is already armed.
If his field is enabled, Field 1*18 for this partition must also be enabled.
Section 5 – Data Field Descriptions