Installing Output Devices; Figure 3-20: 4204 Relay Module; Figure 3-21: 4204Cf Relay Module - Honeywell VISTA-128BPEN Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Table of Contents

Advertisement

Vista-128BPEN Installation and Setup Guide

Installing Output Devices

The VISTA-128BPEN support up to 96 outputs. Each device must be programmed as to how to act (ACTION), when to
activate (START), and when to deactivate (STOP). The 4204, 4204CF, FSA-8, FSA-24, 4101SN and/or X-10 devices may
be used as output devices.
Installing 4204 and 4204CF Relay Modules
Each 4204 module provides 4 relays with Form C (normally open and normally closed) contacts. Each 4204CF module
adds two style Y supervised bell outputs to the system. For 4204CF modules, only relays 1 and 3 on each module can be
programmed.
The relay module will not operate until the device address you have set the DIP switches for is enabled in the
control's Device Programming in the #93 Menu Mode .
To install the relay modules, see Figures 3-20 and 3-21 and perform the following steps:
Step
Action
1
Set the 4204 or 4204CF's DIP switches for a device address 01-15.
Do not use an address being used by another device (keypads, RF receivers, etc.).
2
Mount the 4204 and 4204CF Modules per the instructions provided with them.
3
Connect the module's wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of harness) to
the module.
If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire
run lengths. Refer to the instructions provided with the 4204CF for its maximum permissible wire lengths.
Wire Gauge
#22
#20
#18
#16
3-18
Maximum Length
125 feet
200 feet
300 feet
500 feet
SWITCH
NUMBER
OFF
ON
0
1
2
1
NOT USED
2
ON
ON
3
ON
ON
4
ON
ON
ON
5
ON
ON
ON
SWITCH SHOWN
FOR ADDRESS "0"
4204
DIP SWITCH FOR
SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING
TAMPER
COVER
TAMPER
(REED)
SWITCH

Figure 3-20: 4204 Relay Module

DIP SWITCH:
WHITE AREAS DENOTE SWITCH HANDLES
OFF
POSITION 1
ENABLES/DISABLES COVER TAMPER
ON = TAMPER DISABLED; OFF = TAMPER ENABLED
SHOWN DISABLED (AS SHIPPED).
POSITIONS 2-5
DETERMINE 4204CF'S ADDRESS:
CONTROL'S INSTRUCTIONS SPECIFY ADDRESS TO
USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
4204CF
TB2
12
NOTIFICATION
DIP SWITCH
APPLIANCE
11
NC
FOR SETTING DEVICE
OUTPUT B
ADDRESS AND
10
NC
2K EOLR
ENABLING/DISABLING TAMPER
9
EOL20
POLARIZED
8
NC
NOTIFICATION
COVER TAMPER (REED) SWITCH
7
NC
APPLIANCES
6
NOTIFICATION
4-PIN CONSOLE
APPLIANCE
PLUG
5
EITHER OR BOTH
OUTPUT A
CAN BE USED
4
2K EOLR
3
EOL20
TB1
2
NC
POWER FOR NOTIFICATION APPLIANCE OUTPUTS A & B
1
NC
8-30 VDC OR VFW. UP TO 2.4A DEPENDING ON
13
14
15
16
NOTIFICATION APPLIANCE CURRENT.
YEL
DATA IN FROM CONTROL
BLK
GROUND
GRN
DATA OUT TO CONTROL
RED
12VDC; SUPPLIES POWER TO MODULE CIRCUITRY (INCLUDING APPLIANCE OUTPUT
RELAY COILS). CURRENT DRAIN AY 12V IS: 25mA + (80mA PER ACTIVE OUTPUT).

Figure 3-21: 4204CF Relay Module

4 2 0 4 A D D R E S S S E T T I N G S
("—" means "OFF")
3
4
5
6
7
8
9
10
11
12
13
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
EITHER OR BOTH
CAN BE USED
RELAY
4
TYPICAL
(SHOWN "OFF")
RELAY
3
RELAY
2
4-PIN
CONSOLE
PLUG
RELAY
TB1
1
13 14 15 16
YEL
DATA IN FROM
CONTROL
BLK
(–) GROUND
GRN
DATA OUT
TO CONTROL
RED
(+) 12V
SWITCH
4204CF ADDRESS SETTINGS
ON
NUMBER
("—" means "OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
ON —
ON
ON
ON
ON
ON
ON
2
3
ON ON
ON ON —
ON ON
ON ON
4
ON ON ON ON
ON ON ON ON
5
ON ON ON ON ON ON ON ON —
FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE
MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
SPECIAL APPLICATIONS CIRCUITS
ALARM POLARITY SHOWN
EACH OUTPUT PROVIDES
STYLE Y SUPERVISION
EACH OUTPUT RATED 1.2A MAX
NOTIFICATION APPLIANCE AND CONSOLE DATA
USE NOTIFICATION APPLIANCES
OUTPUTS ARE POWER-LIMITED.
COMPATIBLE WITH POWER SUPPLY
VOLTAGE RATING
ALL POWER-LIMITED WIRING MUST BE SEPARATED
FROM NON-POWER-LIMITED AND HIGH-VOLTAGE
WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED
WHEN POWERED BY THE CONTROL PANEL.
NFPA-72 COMPLIANT.
14
15
ON
TB2
12
C
NC
11
NO
10
9
C
NC
8
7
NO
6
C
5
NC
4
NO
3
C
2
NC
1
NO
4204-01-V1
14
15
ON —
4204CF-004-V1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents