Vista-128BPEN Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
Log Faults & Restores
1*80
0 = disable
1 = enable
Number of Partitions
2*00
Enter 1-8.
Daylight Saving Time Start/End
2*01
Month
0 = disable
1 = enable
Daylight Saving Time Start/End
2*02
Weekend
0 = disable
1 = enable
U L
Fields 2*05 – 2*08 must be set to 0 for UL installations.
Auto-Arm Delay (partition-
2*05
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto arming.
Auto-Arm Warning Period
2*06
(partition-specific)
01-15 times 1-minute warning.
00 = no warning period.
Auto-Disarm Delay (partition-
2*07
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto disarming.
Force Arm Enable for Auto-Arm
2*08
(partition-specific)
0 = disable
1 = enable
Open/Close Reports by
2*09
Exception (partition-specific)
0 = disable
1 = enable
Allow Disarming Only During
2*10
Arm/Disarm Windows (partition-
specific)
0 = disable
1 = enable
5-12
EXPLANATION
When enabled automatically transfers data of the RS232 output.
Home Control Automation is not allowed in UL installations.
Enter the number of partitions used in the system.
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user's region.
Standard setting for U.S. is 03,11.
Enter the start and end weekends for daylight saving time as follows: 1=first;
2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last.
Standard setting for U.S. is 2,1.
This is the time between the end of the arming window and the start of auto-
arm warning time (field 2*06).
This is the time that the user is warned by a keypad sounding and display to
exit the premises prior to auto arming of the system.
This is the time between the end of the disarming window and the start of auto
disarming of the system.
If enabled, the system automatically bypasses any faulted zones when it
attempts to auto-arm.
If disabled, the system does not auto-arm.
NOTE: Force arm is not approved for ULC applications.
If enabled, Open/Close reports are sent only if the openings/closings occur
outside the arm and disarm windows.
NOTES:
Open reports are also suppressed during the closing window in order to
prevent false alarms if the user arms the system, then re-enters the premises,
for example to retrieve a forgotten item.
Openings and closings are still recorded in the event log.
This field must be set to 1 if No Opening and No Closing reports are to be
sent.
If enabled, disarming of the system is allowed only during the
arming/disarming windows, or if the system is in alarm (if 2*11 is set to 1).
NOTE: This applies only to Operator-level users. Installer, Master, and
Manager-level users can disarm the system at any time.