This control complies with National Fire Protection Association (NFPA) requirements for temporal pulse sounding
U L
of fire notification appliances.
Alarm Output Supervision
When supervision is enabled, the VISTA-128BPEN monitors the alarm output wiring for open and short circuit faults
while the output is inactive. The system provides a trouble indication (Zone 970) when an open occurs; or when a short
occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth ground.
NOTE: When supervising the bell output (zone 970), only one device can be connected to the alarm output
U L
(terminals 4 and 5) for UL and Fire installations.
The VISTA-128BPEN indicates the trouble condition regardless of whether the system is armed or disarmed. The zone
displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1.
The Contact ID event code is 321, Bell Trouble. The trouble is cleared from the display by entering the user code + OFF.
Wiring the Alarm Output
The wiring of the alarm output depends upon whether you are going to supervise the output or not. Use the appropriate
procedure below for your application.
U L
Use only UL Listed sounding devices for UL installations.
Compatible Alarm Indicating Devices
Model Number
Device Type
719
Compact Outdoor Siren
(not UL Listed)
747
Indoor Siren
AB12M
Bell
System Sensor
Fire Piezo Horn
HR
System Sensor
Fire Horn/Strobe
P2RK, P4RK
Wheelock
Fire Horn/Strobe
AS-121575W
Polarizing Diode
Yes
Yes
Yes
No
No
No
1
2
3
+
ALARM SOUNDER OUTPUT:
1-VDC - 13.8VDC
1.7A MAXIMUM

Figure 3-6: Wiring Polarized Fire Devices

POLARIZING DIODES
(MUST MOUNT AT INDICATING DEVICE)
PANEL BELL
BELL
PANEL BELL
NONPOLARIZED BURGLARY
INDICATING DEVICES

Figure 3-7: Wiring Nonpolarized Burglary Devices

4
5
6
7
8
-
+
-
BELL
HORN
HORN
BELL
POLARIZED FIRE
INDICATING DEVICE
Installing the Control
TO
OTHER
DEVICES
non_polar_devices
3-5