02.98

EMC measures

Screen connection
The screens of pre–assembled original manufacturer's cables are automatically
cables
connected when the connector is inserted.
Exceptions:
Refer to P.1-52 for further measures.
Connecting–up the
In order to ensure a good connection between the front panel and the housing,
shield to the front
the front panel screws must be tightened up to 0.8 Nm.
panel
Connecting the
Terminal X131 (electronics ground): Refer to Fig. 9-1.
electronics ground
Protection against
A varistor module, Order No. 6SN1111–0AB00–0AA0 can be inserted at con-
overvoltages
nector X181 on the NE module to protect against overvoltage (line supply net-
works not conforming to VDE (not necessary for UE 5 kW and the monitoring
module).
Additional
measures
Note
All of the measures described here are only valid for supply networks which are
not compatible with VDE. In normal industrial supply networks, it is guaranteed,
without having to use other measures that the disturbance and noise values
remain below the permissible limits, thus ensuring disturbance–free operation
1-156
– Setpoint cable from an analog NC.
In this case, the screens of the setpoint pairs must be connected to the
upper side of the module. The threaded holes can be used for this pur-
pose. (M5x10/3 Nm).
– Drive bus cable from SINUMERIK 840C.
In this case, the screen is connected to the above mentioned threaded
hole using the clamp provided.
– Drive bus– and equipment bus extensions for two–tier designs.
In this case, the screens at each end of the cable must be connected to
the above mentioned threaded holes using the clamps provided.
– Motor power cables
The screens of the motor power cables are connected to the screen con-
necting plates (accessories) of the modules using the clamp connectors
provided.
Siemens AG 1998 All Rights reserved
9.9 EMC measures
6SN1197–0AA00 02.98 Edition