Siemens SIMODRIVE 611A Installation And Planning Manual page 121

Transistor pwm inverters and motors for ac feed drives
Table of Contents

Advertisement

07.94
Power–on
Main switch: OFF
Adapt the module to the motor,
standard settings, Section 1
Start–up with battery box
- Connect terminals 48, 63, 64, 663 to terminal 9
- Switch (open) between terminals 65 and 9
Terminals 56/14 at the battery box
Main switch: ON
Set 0 V setpoint at the battery box
Briefly enable term.65 (inching)
Enter a low setpoint
(e. g. 0.1 V)
Briefly enable term.65
Siemens AG 1997 All Rights reserved
SIMODRIVE 611A Installation and Start–Up Guide/IAA/–04.97 Edition
Yes fault
Motor
accelerates?
No
No fault
Does drive run
continuously ?
Yes
1
Feed modules (VS)
Check the motor–PWM inverter connection:
L1, L2, L3 interchanged?
Cable for power connection
Cable for rotor position and tachometer
Main switch: OFF
Open–up the connection between
term.63 and term.9
7 Power –on
VS
1-121