Link Dedicated Instruction Not Complete - Mitsubishi Electric Melsec QJ71LP21 Reference Manual

Q corresponding melsecnet/h network system
Hide thumbs Also See for Melsec QJ71LP21:
Table of Contents

Advertisement

8
TROUBLESHOOTING
Check item
Did an error occur while the transient transmission was
being executed?
Are the routing parameter settings correct?
Is the network No. parameter correct?
A dedicated link instruction is not responded within specified
time.
Does the transmission go through the network module on
the standby system in the redundant system?
The dedicated link instruction executed in the multiple CPU
No. specification does not access the target CPU.
Is the number of resends set every time the instruction is
executed?

8.2.10 Link dedicated instruction not complete

Check item
Is the link dedicated instruction issuing station online?
8 - 30
(2) The transient transmission is not normal
Check the error code at the transient transmission execution and correct the
error according to the error code table in Section 8.3.
Confirm whether a dedicated link instruction is executed to a programmable
controller CPU other than the redundant CPU with the control or standby
system specified. (Error code: 4B00
Check if a dedicated link instruction is executed for a CPU other than the
QCPU in the multiple CPU No. specification. (Error code: 4100
FE20
)
H
Confirm whether a dedicated link instruction is executed to a single CPU
system with a multiple CPU number specified. (Error code: 4B00
Check if a non-existing multiple CPU No. is specified in the target station
type. (Error code: 4B00
)
H
Check that the communication target is not set for a station on another
network No. If it is set for a station on another network No., correct the set
value of the routing parameter. (Refer to Section 7.4.2.)
Check the routing parameters with the communication test of GX Developer's
network diagnostics.
Check the network No. parameter.
If the parameter is not set, the network No. has been set to 1 (default); so
check other station's network No..
Confirm whether a value out of the set range is set for the target station CPU
type.
Using the RTWRITE instruction, change the routing parameter so that
transmission will go through the network module on the control system.
<When the dedicated link instruction is started from the QnACPU>
Not executable for the QnACPU.
<When the dedicated link instruction is started from the QCPU>
Check whether the QCPUs and network modules of the host station and
target station are the following versions.
QCPU: Serial number (first five digits) "06092" or later
Network module: Serial number (first five digits) "06092" or later
Check if the group or all stations has been specified for the target station
number. (Refer to Section 2.2.2 (5).)
Confirm whether a program requires the setting of the number of resends
when executing instructions.
Place the link dedicated instruction issuing station online and execute the link
dedicated instruction.
Use SB0043 as an interlock to confirm the online status in the sequence
program.
MELSEC-Q
Checking procedure
)
H
Checking procedure
, 4B00
,
H
H
)
H
8 - 30