Mitsubishi Electric Melsec QJ71LP21 Reference Manual page 214

Q corresponding melsecnet/h network system
Hide thumbs Also See for Melsec QJ71LP21:
Table of Contents

Advertisement

6
PROGRAMMING
No.
SB0009
Clear loop switch count
SB0091
Forward loop status
SB0095
Reverse loop status
SB0099
Forward loop loopback
SB009A
Reverse loop loopback
6 - 21
(6)
Checking the forward/reverse loop in the optical loop system
The forward/reverse loop in the optical loop system can be checked not only in
the network diagnostics of GX Developer but also with link special relays (SB)
and link special registers (SW). (Refer to Sections 8.1.1 and 8.1.2.)
(a)
Checking the forward/reverse loop of another station
1)
When an error occurs on the forward or reverse loop, the following
link special relay (SB) is turned ON.
• Forward loop status (SB0091)
• Reverse loop status (SB0095)
2)
The station where an error occurred can be identified with the
following link special registers (SW).
• Forward loop status of each station (SW0091 to SW0094)
• Reverse loop status of each station (SW0095 to SW0098)
3)
If loop switching occurs, the cause of the loop switching is stored in
Loop switch data (SW00D0 to SW00DF).
The position of the loop switch data storage can be checked with Loop
switch data pointer (SW00CF).
4)
Cable disconnection or station failure causes loopback.
When loopback occurs, any of the following link special relays (SB) is
turned ON.
• Forward loop loopback (SB0099)
• Reverse loop loopback (SB009A)
5)
The station where loopback occurred can be identified with the
following link special registers (SW).
• Loopback station (forward loop side) (SW0099)
• Loopback station (reverse loop side) (SW009A)
6)
An optical fiber cable reverse insertion (IN-IN, OUT-OUT) can be
checked with Loop usage status of each station (SW009C to SW009F).
7)
The count of loop switching can be checked with Number of loop
switches (SW00CE).
8)
Turning ON Clear loop switch count (SB0009) can clear SW00CE to
SW00DF.
Description
No.
SW0091 to SW0094 Forward loop status of each station
SW0095 to SW0098 Reverse loop status of each station
SW0099
Loopback station (forward loop side)
SW009A
Loopback station (reverse loop side)
SW009C to SW009F Loop usage status of each station
SW00CE
Number of loop switches
SW00CF
Loop switch data pointer
SW00D0 to
Loop switch data
SW00DF
MELSEC-Q
Description
6 - 21

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading