Mitsubishi Electric Melsec QJ71LP21 Reference Manual page 416

Q corresponding melsecnet/h network system
Hide thumbs Also See for Melsec QJ71LP21:
Table of Contents

Advertisement

8
TROUBLESHOOTING
QCPU QJ71LP21-25
8 - 32
(2) Example of checking SW009C to SW009F
An example of incorrect cable connection at Station No. 2 is shown below.
(a) Wiring diagram
Station No. 1
Station No. 2
QCPU QJ71LP21-25
IN
OUT
IN
(b) SW009C to SW009F status
Station No.
Station No. 1
Station No. 3
Station No. 4
Station No. 2
Cables are connected to wrong connectors
at Station No. 2 (connected OUT-OUT with
Station No. 1 and IN-IN with Station No. 3).
Station No. 3
QCPU QJ71LP21-25
OUT
IN
Only Station No. 2 (bit 1) is ON or OFF.
b15
SW009C
SW009D
SW009E
SW009F
All stations (bit 0, bit 2, bit 3) other than Station No. 2 (bit 1) are ON or OFF.
SW009C
SW009D
SW009E
SW009F
Station No. 4
QCPU QJ71LP21-25
OUT
IN
OUT
SW009C to SW009F status
to
b4
0
0
0
0
b15
to
b4
0
0
0
0
MELSEC-Q
b3
b2
b1
b0
0
0
1
0
b3
b2
b1
b0
1
1
0
1
8 - 32