5.2 Network Settings

5.2.1 Starting I/O No.

5.2.2 Network No.

5 - 9
These parameters are used to configure the MELSECNET/H network.
Set the start I/O No., network No., total stations, group No. and mode for each of the
module model names set in the number of modules settings.
Set the start I/O No. to which the module is mounted in 16-point units in hexadecimal
for each applicable network module.
For example, set 130 when the network module is mounted onto X/Y130 to 14F.
Q61P
QCPU QX42
QX42
64 pts 64 pts 32 pts 32 pts 32 pts 32 pts
40
00
H
H
to
X/Y
to
7F
3F
H
H
(1)
Valid setting range
0
to 0FE0
(The I/O point range of the CPU module)
H
H
(2)
Precaution
Unlike the setting method for the AnUCPU (only first two digits of the
3-digits are used for setting), all three digits are used for setting.
Set the network number to which the applicable network module is connected.
(1)
Setting range
1 to 239
(2)
Precautions
(a)
For standby stations, set the network numbers that are differently from
regular stations.
Regular
Standby
station
CPU QJ71 QJ71
1M
1 2M
P
P
(b)
The same network number can be set for normal stations.
Control
Control
station
station
CPU
QJ71
QJ71
1M
1
1M
2
P
P
QX41
QY41
QY41
QY41
Empty
48 pts
80
A0
C0
E0
100
H
H
H
H
to
to
to
to
to
9F
BF
DF
FF
12F
H
H
H
H
Regular
station
station
CPU QJ71 QJ71
1
1N
2
S
Network No. 1 (regular)
Network No. 2 (standby)
Normal
Normal
station
station
1N
3
1N
S
Network No. 1
QJ71
32 pts
130
H
H
to
14F
H
H
Standby
Regular
station
station
CPU QJ71 QJ71
2N
2
1N
S
S
4
S
MELSEC-Q
Standby
station
3
2N
3
S
5 - 9