6
PROGRAMMING
No.
Parameter communication status of each
SB0078
station
SB007C
Parameter status of each station
SB01E0
Network type consistency check
6 - 25
(9)
Checking parameter status
The reflection status and setting contents of parameters can be checked with link
special relay (SB) and link special register (SW).
(a)
Checking parameter status of other stations
1)
Check the following link special relay (SB) and link special register
(SW) with the master station.
• When receiving parameters is completed, Parameter
communication status of each station (SB0078) is turned OFF.
• Stations that are still communicating parameters can be checked
with Parameter communication status of each station (SW0078 to
SW007B).
2)
Check the following link special relay (SB) and link special register
(SW) with the master station.
• When parameters have an error, Parameter status of each station
(SB007C) is turned ON.
• The station No. of the faulty station is stored in Parameter error
status of each station (SW007C to SW007F).
3)
When the network type of the control station is different from that of a
normal station, Network type consistency check (SB01E0) is turned
ON.
The station number of different network type is stored in Network type
consistency check (SW01E0 to SW01E3).
4)
Details of the parameters for each station can be checked with the
link special relay (SB) and link special register (SW) of each station.
(Refer to (9)(b) in this Section)
Description
No.
SW0078 to
Parameter communication status of each
SW007B
station
SW007C to
Parameter error status of each station
SW007F
SW01E0 to
Network type consistency check
SW01E3