Mitsubishi Electric Melsec QJ71LP21 Reference Manual page 461

Q corresponding melsecnet/h network system
Hide thumbs Also See for Melsec QJ71LP21:
Table of Contents

Advertisement

APPENDICES
No.
Name
SW0039
Send/receive instruction
(57)
(5) processing result
SW003B
Send/receive instruction
(59)
(6) processing result
SW003D
Send/receive instruction
(61)
(7) processing result
SW003F
Send/receive instruction
(63)
(8) processing result
SW0040
Network No.
(64)
SW0041
Group No.
(65)
SW0042
Station No.
(66)
SW0043
Mode status
(67)
SW0044
Station setting
(68)
App - 22
Table 4 Link special Register (SW) List (continued)
Description
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 5 is used).
0
: Normal completion
Other than 0 : Abnormal completion (Refer to the error codes
in Section 8.3)
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 6 is used).
0
: Normal completion
Other than 0 : Abnormal completion (Refer to the error codes
in Section 8.3)
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 7 is used).
0
: Normal completion
Other than 0 : Abnormal completion (Refer to the error codes
in Section 8.3)
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 8 is used).
0
: Normal completion
Other than 0 : Abnormal completion (Refer to the error codes
in Section 8.3)
Stores the network number of the host.
Range: 1 to 239
Stores the group number of the host.
0
: No group designation
1 to 32
: Group No.
Stores the station No. of host station.
1 to 64
: Station No.
7D
: Remote master station
H
Stores the mode status of the host.
0
: Online
2
: Offline
3 or more
: Applicable test
On inter-PLC network: Stores the condition setting switch status
of the host.
0: Off
1: On
b15 b14
b13
b12
b10
b9
b8
b7
b11
0 0
0
0
0
0
SW0044
Operation mode
(0: Online mode, 1: Debug mode)
Host station network type
(0: MELSECNET/H mode, MELSECNET/10 mode,
1: MELSECNET/H Extended mode)
b6
to
b2
b1
b0
0
to
0
0
Network type
(0: PLC to PLC network)
Station type
(0: Normal station, 1: Control station)
Control station operation
(0: Switch to designated control station,
1: Keep current control station)
[Availability column] Loop: optical loop, Bus: coaxial/twisted bus
MELSEC-Q
Use permitted/prohibited
Remote
Control
Normal
master
station
station
station
Loop
Bus
Loop
Bus
Loop
: Available,
Remote I/O
station
Bus
Loop
Bus
: Not available
App - 22

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents