8
TROUBLESHOOTING
Error No.
F706
Received data size error
F707
Number of relay stations invalid
F708
Receiving group number error
F709
Receiving network number error
F70A
System error
F70B
Response wait timeout
F70C
System error
F70E
System error
F710
System error
F711
System error
F712
System error
F781
Connection target specification error
F782
System error
F783
System error
F7C1
Host station channel in use
F7C2
Target station channel in use
8 - 42
Table 8.1 Error code list (continued)
Description of error
The cable is faulty, or The hardware of the network module is faulty.
If a communication error has occurred, review the cable.
If not, the hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
Set stations to which data can be sent.
Review the system.
Review the routing parameters.
Review the group number of the target station.
Review the network No. of network parameter for a host station and a target
station.
If the parameter is not set, the network No. is preset to 1 (default); so check the
network No. of other stations.
The cable is faulty, or the hardware of the network module is faulty.
If a communication error has occurred, review the cable.
If not, the hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
Wait until SB0047 (baton pass status) and SB0049 (data link status) are
recovered.
The cable is faulty, or the hardware of the network module is faulty.
If a communication error has occurred, review the cable.
If not, the hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
Check if C24 connection or CC-Link connection is specified for access to other
stations.
If the setting is correct, the hardware of the CPU or network module is faulty.
Please consult your local Mitsubishi representative.
The hardware of the CPU or network module is faulty.
Please consult your local Mitsubishi representative.
The hardware of the network module is faulty.
Please consult your local Mitsubishi representative.
The same channel cannot be used at the same time.
Change the channel number.
Alternatively, do not use the same channel at the same time.
Retry the SEND instruction after a little while.
Check if the target station uses the channel concerned to execute the
instruction, or if RECV processing is executed.
Check if another station executes the SEND instruction to the target station's
channel.
MELSEC-Q
Corrective measure
8 - 42

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading