5
PARAMETER SETTINGS

5.5 Control Station Return Setting

5 - 20
This parameter is used to specify the type of station used by the control station when
returning to the network in the control station return control function (Refer to Section
3.2.2).
Select this parameter to make the control station return as a normal station without
stopping the baton pass in the system in operation.
The control station return setting is required only for the control station.
(1)
When "Return as control station" is selected (default)
The baton pass (cyclic transmission, transient transmission, etc.) temporarily
stops because the control station sends the parameters to the normal stations
and returns to the network.
(2)
When "Return as normal station" is selected
The control station returns to the network as a normal station, without stopping
the baton pass in the network.
[Setting screen]
REMARKS
• When "Return as control station" is selected, the network stop time becomes
longer because the baton pass is stopped, but the common parameters can easily
be changed only by resetting the CPU of the control station.
• If "Return as normal station" is selected, the network does not stop because the
control station returns to the network without stopping the baton pass.
However, it is necessary to reset the CPUs of all the stations after changing the
common parameters of the control station while the network is in operation. If only
the CPU of the control station is reset, a parameter mismatch error is detected in
the control station and it is disconnected from the network.
MELSEC-Q
5 - 20