APPLICATION FUNCTIONS
7 - 8
Precautions
1)
Do not set the Transfer to device range of the network module within the
refresh range of the network. Otherwise, the correct data cannot be sent to
other stations.
Refresh range
Refresh range
2)
The transfer data is sent to the transfer to network via the network module; it is
not stored in the transfer to device range of the network module.
When using the transfer data in the relay station, the transfer to data must be
transferred to the device on the CPU side by link refreshing.
POINT
When it is necessary to set 65 or more transfer ranges for the inter-link data
transfer function, the data must be transferred from the transfer from to the
destination in the sequence programs using the MOV instruction, etc.
(3) Available inter-link data transfer stations
As shown in the table below, the control stations and normal stations are
available.
Transfer from
Control station
MELSEC
Normal station
NET/H
Standby station
CPU
Network module 1
Transfer to
Control station
MELSEC-Q
Network module 2
Transfer
to
MELSECNET/H
Normal station
: Available
Transfer
from
Standby station
: Not available