APPLICATION FUNCTIONS
Device
Item
Target station's
(S1)+3
CPU type
Target station
(S1)+4
network No.
Target station No.
(S1)+5
8
5: The setting side is as shown below.
User
: It is data the user sets in the sequence program before execution of a link dedicated instruction.
System: The programmable controller CPU stores the execution result of the link dedicated instruction.
6: The CPU type can be specified when the host station is a network module of which function version is either D or later or the following.
• Network module: Serial number (first five digits) "10101" or later
(The CPU module cannot be specified in the case other than the above. Only access to the control CPU is available.)
7: The CPU type can be specified when the QCPUs and network modules of the host station or target station are the following versions.
• Network module: Serial number (first five digits) "06092" or later
• QCPU: Serial number (first five digits) "06092" or later
(The CPU module cannot be specified in the case other than the above. Only access to the control CPU is available.)
8: When a CPU in a multiple CPU system is specified for the target station CPU type ((S1)+3) and group specification (81
specified for the target station number ((S1)+5), the instruction is executed for only the system where the CPU in the multiple CPU system specified for the
target station CPU type is the control CPU of the target station.
Refer to Section 2.2.2 (5) for details.
7 - 63
Specify the CPU module on the station to be accessed.
Setting value
Control CPU (The access target is the same as when "03FF
0000
H
specified.)
03D0
6
Control system CPU
H
03D1
6
Standby system CPU
H
03D2
6
System A CPU
H
03D3
6
System B CPU
H
 Control CPU (single CPU system)
03E0
7
H
 Multiple CPU system No.1
03E1
7
Multiple CPU system No.2
H
03E2
7
Multiple CPU system No.3
H
03E3
7
Multiple CPU system No.4
H
03FF
6
Control CPU
H
When the instruction is executed with control system CPU (03D0
(03D1
) specified, if system switching occurs at the target station, the instruction execution
H
may fail. (Error code: 4244
, 4248
H
If the instruction has failed with the above error, execute it again.
Specify the network No. of the target station.
1 to 239
: Network No.
254
: Specify this when 254 has been set in Jn.
Specify the station No. of the target station.
1) Station No. specification
: Station No.
1 to 64
(To increase the reliability of data, it is recommended to execute the
instruction with the execution type in (S1)+0 set to "1: With arrival
confirmation".)
2) Group specification
: All stations in group No.1 to 32
81
to A0
H
H
(Setting is available when the execution type is set to "0: No arrival
confirmation" in (S1)+0.)
3) All stations specification
: All stations of the target network No. (Except the host station)
FF
H
(Setting is available when the execution type is set to "0: With arrival
confirmation" in (S1)+0.)
When a group is specified, set the group No. of the target station with the network
parameters from GX Developer.
Setting data
Description
) or standby system CPU
H
)
H
MELSEC-Q
Setting range
" is
H
0000
H
03D0
to 03D3
H
H
03E0
to 03E3
H
H
03FF
H
1 to 239
254
1 to 64
81
to A0
H
H
FF
H
(Continued to the next page)
to A0
) or all stations (FF
H
H
Setting
side
5
User
User
User
) is
H
7 - 63